WSE • 3/21/97 16720 17 SE 6000 Security Management System
9. Operator Definable Alarm Task Programming:
a. Tasks available: 100 per event minimum.
b. The operator shall be provided with the capability to define a set of tasks to be performed by
the system as a result of a specific action. For example, an event such as an alarm condition
(smoke detector activated), access event (invalid access attempt) or time trigger (60 seconds
after a duress button was pressed) shall initiate a task or series of tasks.
c. The tasks performed may consist of activation of an output relay and/or control commands
sent to a CCTV switcher.
H. Additional Security Operations:
1. [Elevator Control (optional module on SE 60xx):
a. General:
1) Elevator Control shall be provided via software which provides complete floor by floor
access control for elevator cars by allowing activation of only those buttons which control
floor access as defined for each specific cardholder.
2) Elevator Control shall operate without dependence upon any particular elevator panel,
thus allowing interface with virtually any commercial elevator operating system.
b. Elevator Control capabilities include:
1) Floor by Floor Cardholder Access Control:
(i) As a card is presented to a reader installed within the elevator car, dependent upon
the access privileges previously defined, specific floor buttons are enabled to allow
specific floor access.
(ii) The floor buttons remain enabled for a user-definable length of time before
automatically defaulting to the deactivated mode.
2) Multiple Hardware Support for Output Control:
(i) The Elevator Control program shall interface with WSE Controllers, and Opto 22
input/output multiplexor devices to control the enabling and disabling of elevator
buttons.
3) Controllable Fail-soft Operation:
(i) In conjunction with Opto 22 multiplexor boards controlling output contacts, the
Elevator Control option shall provide for the programming of the elevator button
profile in the event of lost communications with Host computer.
(ii) This form of watchdog operation provides the capability of enabling specific buttons,
as required, during a communications failure.
4) The Elevator Control software shall be included as part of the basic application on a high
end (SE 6100, 6200, 6300) system.]
2. [CCTV Control (optional module):
a. General:
1) Closed Circuit Television communication interface shall enable the system to monitor
and control specific elements of a CCTV system through the security management
system.
b. Functions:
1) Camera/Monitor Control:
(i) Manual selection of the camera scene for viewing on CCTV monitors from Host,
thus eliminating the requirement for remote switcher control.
(ii) Response to system events shall be provided to allow the assignment of a specific
camera scene to a specific monitor at the occurrence of a pre-defined alarm
condition. When camera sequencing is enabled, the system shall provide the
capability to halt the sequencing and display the requested camera scene at a specific
monitor. Sequencing shall then be re-initiated at the discretion of the operator.
(iii) Preset camera and monitor control shall be provided to preset the pan, tilt, zoom and
focus for optimum view of a particular area or location.